Electric Motor Torque Calculator (N·m and lb-ft)

Calculate mechanical shaft torque in Newton-meters (N·m) and pound-feet (lb-ft), alongside angular velocity (rad/s), for any AC or DC electric motor.

Mechanical Input Parameters

kW

Rated mechanical shaft power delivered to load.

RPM (rev/min)
✓ Instant calculation

Calculated Shaft Torque

Metric Shaft Torque
49.74Newton-meters (N·m)
Imperial Torque
36.68lb-ft (pound-feet)
Angular Velocity (ω)
150.80rad/s (radians/sec)
Formula Substitution:
T (N·m) = (30,000 / π) × (7.50 kW / 1440 RPM) = 49.74 N·m
T (lb·ft)= 49.74 N·m / 1.355818 = 36.68 lb-ft
ω (rad/s)= (2π × 1440 RPM) / 60 = 150.80 rad/s
✓ Copied to clipboard!

How to Calculate Electric Motor Torque

Torque is the rotational force produced by an electric motor's shaft. In physical mechanics, mechanical power is defined as the product of rotational torque (T) and angular velocity (omega):

Fundamental Rotational Power Equation:

P (Watts) = Torque (N·m) × ω (rad/s)

Where ω = (2π × RPM) / 60

Rearranging this relationship yields the standard engineering formula for electric motor torque based on shaft power in kilowatts:

Torque (N·m) = (60,000 / 2π) × (PkW / NRPM) = 9549.29658553 × (PkW / NRPM)

Engineering textbooks commonly round the constant 9549.3 to 9550 for rapid mental estimation. This calculator uses the full precision constant 30,000 / π.

Imperial Torque Equation (Horsepower & Pound-Feet)

In North American industrial practice governed by NEMA standards, motor power is specified in mechanical horsepower (HP) and shaft torque in pound-feet (lb-ft).

Because one mechanical horsepower equals 33,000 ft-lb/min, dividing by 2π radians yields the widely used constant 5252:

Imperial Torque Equation:

Torque (lb·ft) = [Power (HP) × 5252.113] / Rotational Speed (RPM)

The 5252 RPM Crossover Point: A mathematical consequence of this equation is that at exactly 5,252 RPM, an engine or motor's horsepower and torque (in lb-ft) are numerically identical. Below 5,252 RPM, torque is numerically greater than horsepower; above 5,252 RPM, horsepower is numerically greater than torque.

Full-Load Torque vs. Starting and Breakdown Torque

The value computed by this tool represents rated continuous full-load torque (T_FLT). When selecting an electric motor for an industrial machine, three distinct torque points must be considered:

1. Locked-Rotor Torque (LRT)

The torque produced at zero speed during startup. For standard NEMA Design B motors, LRT is typically 150% to 250% of full-load torque to overcome stationary load stiction.

2. Pull-Up Torque (PUT)

The minimum torque developed during acceleration from standstill to the breakdown point. The motor stalls if load torque exceeds pull-up torque.

3. Breakdown Torque (BDT)

The maximum peak torque the motor can sustain at rated voltage without an abrupt drop in speed (stall). Typically 200% to 300% of rated full-load torque.

Frequently Asked Questions — Motor Torque

How to calculate electric motor torque from power and RPM?▼

For metric units: Torque (N·m) = 9549.3 × Power (kW) / Speed (RPM). For imperial units: Torque (lb-ft) = 5252.1 × Power (HP) / Speed (RPM). Example: a 7.5 kW motor at 1440 RPM produces 9549.3 × 7.5 / 1440 = 49.7 N·m (36.7 lb-ft). Always use the rated full-load RPM from the nameplate, not the synchronous speed.

Should I use synchronous speed or full-load RPM to calculate motor torque?▼

Always use the rated full-load RPM stamped on the motor nameplate, not synchronous speed. AC induction motors always run slightly below synchronous speed due to slip (typically 1–5%). A 4-pole, 50 Hz motor has synchronous speed 1500 RPM but nameplate speed might read 1450 or 1460 RPM. Using the actual nameplate RPM gives accurate full-load torque.

Why does torque decrease when motor speed increases?▼

For a constant mechanical power output, torque is inversely proportional to angular velocity (P = T × ω). As speed doubles, the torque required to deliver the same shaft power halves. For example: a 10 kW motor at 1000 RPM produces 95.5 N·m; the same 10 kW at 2000 RPM produces only 47.7 N·m.

How do you convert between Newton-meters (N·m) and pound-feet (lb-ft)?▼

Multiply Newton-meters by 0.73756 to get pound-feet (1 N·m = 0.73756 lb-ft). Multiply pound-feet by 1.35582 to get Newton-meters (1 lb-ft = 1.35582 N·m). Example: 50 N·m = 50 × 0.73756 = 36.88 lb-ft. This calculator automatically outputs both units.

What is the difference between rated torque, starting torque, and breakdown torque?▼

Rated full-load torque (FLT) is the continuous torque at nameplate power and speed. Starting torque (Locked-Rotor Torque, LRT) is produced at zero speed during startup — typically 150% to 250% of FLT for NEMA Design B motors. Breakdown torque (BDT) is the peak torque the motor can sustain before stalling — typically 200% to 300% of FLT. This calculator computes rated full-load torque only.

How to calculate motor torque from current and voltage?▼

First, calculate mechanical output power from electrical inputs: for three-phase, P_out (kW) = √3 × V × I × PF × (η / 100) / 1000; for single-phase, P_out (kW) = V × I × PF × (η / 100) / 1000. Then apply the torque formula: Torque (N·m) = 9549.3 × P_out / RPM. You need the efficiency (η) and power factor (PF) values from the motor nameplate.