Single-Phase Motor Current Formula and Calculations
Single-phase AC induction motors are widely utilized in residential, commercial, and light industrial equipment such as air conditioning compressors, domestic water pumps, power tools, and ventilation fans.
Single-Phase Current Formula:
I (Amperes) = [Pinput (kW) × 1000] / [V × cos φ]
Where Pinput = Poutput / (η / 100)
Notice that unlike three-phase systems, the factor of square root of 3 (approx. 1.732) is not present. Consequently, for an identical mechanical power output and voltage rating, a single-phase motor draws approximately 1.73 times more current than a comparable three-phase motor.
Standard Single-Phase Full-Load Currents (NEC Table 430.248)
The National Electrical Code (NEC Table 430.248) specifies standardized full-load currents for sizing branch circuits, disconnect switches, and protective devices:
| Motor Power | 115 Volts | 120 Volts | 230 Volts | 240 Volts |
|---|---|---|---|---|
| 1/4 HP (0.19 kW) | 5.8 A | 5.6 A | 2.9 A | 2.8 A |
| 1/2 HP (0.37 kW) | 9.8 A | 9.4 A | 4.9 A | 4.7 A |
| 1 HP (0.75 kW) | 16.0 A | 15.3 A | 8.0 A | 7.7 A |
| 2 HP (1.5 kW) | 24.0 A | 23.0 A | 12.0 A | 11.5 A |
| 5 HP (3.7 kW) | 56.0 A | 53.7 A | 28.0 A | 26.8 A |
Frequently Asked Questions
How to calculate single-phase motor full-load current (FLA)?▼
Single-phase full-load current is calculated as: I (Amperes) = (P_shaft × 1000) / [V × cos φ × (η / 100)], where P_shaft is shaft mechanical power in kW (or HP × 0.7457), V is RMS line voltage (115V, 120V, 230V, or 240V), cos φ is power factor, and η is efficiency (%).
How many amps does a 1 HP single-phase motor draw?▼
According to standard NEC Table 430.248, a 1 HP single-phase motor draws approximately 16.0 Amperes at 115 Volts and 8.0 Amperes at 230 Volts (at 120V ~15.3 A, at 240V ~7.7 A). Always consult the motor nameplate for specific applications.
Why does a 230V motor draw half the current of a 115V motor for the same power?▼
Electrical power is the product of voltage, current, and power factor (P = V × I × cos φ). Because total power required is constant, doubling operating voltage from 115V to 230V cuts required line current by exactly 50%, reducing resistive I²R heat losses in conductors by 75%.
How high is single-phase motor starting current compared to running current?▼
Single-phase induction motors typically experience starting inrush currents (Locked-Rotor Amperes) that are 5 to 7 times their rated full-load amperes until the centrifugal switch disconnects the auxiliary start winding around 75% to 80% synchronous speed.
How many amps does a 1/2 HP and 2 HP single-phase motor draw?▼
According to NEC Table 430.248: A 1/2 HP single-phase motor draws 9.8 A at 115V and 4.9 A at 230V. A 2 HP single-phase motor draws 24.0 A at 115V and 12.0 A at 230V.
How to calculate single-phase motor current from kW?▼
To calculate single-phase motor current from shaft power in kilowatts: Current (Amps) = (Power in kW × 1000) / (Voltage × Power Factor × Efficiency). For example, a 1.5 kW motor at 230V with 0.80 PF and 75% efficiency draws: (1.5 × 1000) / (230 × 0.80 × 0.75) = 1500 / 138 ≈ 10.87 Amperes.