Single-Phase Motor Current Calculator (FLA)

Determine steady-state full-load running current (Amps), electrical real input power (kW), and total apparent power (kVA) for 115V, 208V, 230V, and 240V single-phase electric motors.

Single-Phase Input Parameters

HP

Rated shaft mechanical output power.

Volts

Typical single-phase range: 0.65 to 0.82 (PSC motors: ~0.90).

%

Standard single-phase efficiency: typically 65% to 80%.

✓ Instant calculation

Calculated Single-Phase Amps

Full-Load Current (FLA)
6.01Amperes (A)

Steady-state line current drawn under 100% rated shaft load.

Input Real Power (Pin)
1.04kW
Apparent Power (S)
1.38kVA
Reactive Mag. (|Q|)
0.91kVAR
Formula Substitution:
P_in = (1.00 HP × 0.746) / 0.72 = 1.04 kW
I = (1.04 kW × 1000) / (230 V × 0.75) = 6.01 A
S = (230 V × 6.01 A) / 1000 = 1.38 kVA
|Q| = √(1.38² − 1.04²) = 0.91 kVAR
✓ Copied to clipboard!

Single-Phase Motor Current Formula and Calculations

Single-phase AC induction motors are widely utilized in residential, commercial, and light industrial equipment such as air conditioning compressors, domestic water pumps, power tools, and ventilation fans.

Single-Phase Current Formula:

I (Amperes) = [Pinput (kW) × 1000] / [V × cos φ]

Where Pinput = Poutput / (η / 100)

Notice that unlike three-phase systems, the factor of square root of 3 (approx. 1.732) is not present. Consequently, for an identical mechanical power output and voltage rating, a single-phase motor draws approximately 1.73 times more current than a comparable three-phase motor.

Standard Single-Phase Full-Load Currents (NEC Table 430.248)

The National Electrical Code (NEC Table 430.248) specifies standardized full-load currents for sizing branch circuits, disconnect switches, and protective devices:

Motor Power115 Volts120 Volts230 Volts240 Volts
1/4 HP (0.19 kW)5.8 A5.6 A2.9 A2.8 A
1/2 HP (0.37 kW)9.8 A9.4 A4.9 A4.7 A
1 HP (0.75 kW)16.0 A15.3 A8.0 A7.7 A
2 HP (1.5 kW)24.0 A23.0 A12.0 A11.5 A
5 HP (3.7 kW)56.0 A53.7 A28.0 A26.8 A

Frequently Asked Questions

How to calculate single-phase motor full-load current (FLA)?▼

Single-phase full-load current is calculated as: I (Amperes) = (P_shaft × 1000) / [V × cos φ × (η / 100)], where P_shaft is shaft mechanical power in kW (or HP × 0.7457), V is RMS line voltage (115V, 120V, 230V, or 240V), cos φ is power factor, and η is efficiency (%).

How many amps does a 1 HP single-phase motor draw?▼

According to standard NEC Table 430.248, a 1 HP single-phase motor draws approximately 16.0 Amperes at 115 Volts and 8.0 Amperes at 230 Volts (at 120V ~15.3 A, at 240V ~7.7 A). Always consult the motor nameplate for specific applications.

Why does a 230V motor draw half the current of a 115V motor for the same power?▼

Electrical power is the product of voltage, current, and power factor (P = V × I × cos φ). Because total power required is constant, doubling operating voltage from 115V to 230V cuts required line current by exactly 50%, reducing resistive I²R heat losses in conductors by 75%.

How high is single-phase motor starting current compared to running current?▼

Single-phase induction motors typically experience starting inrush currents (Locked-Rotor Amperes) that are 5 to 7 times their rated full-load amperes until the centrifugal switch disconnects the auxiliary start winding around 75% to 80% synchronous speed.

How many amps does a 1/2 HP and 2 HP single-phase motor draw?▼

According to NEC Table 430.248: A 1/2 HP single-phase motor draws 9.8 A at 115V and 4.9 A at 230V. A 2 HP single-phase motor draws 24.0 A at 115V and 12.0 A at 230V.

How to calculate single-phase motor current from kW?▼

To calculate single-phase motor current from shaft power in kilowatts: Current (Amps) = (Power in kW × 1000) / (Voltage × Power Factor × Efficiency). For example, a 1.5 kW motor at 230V with 0.80 PF and 75% efficiency draws: (1.5 × 1000) / (230 × 0.80 × 0.75) = 1500 / 138 ≈ 10.87 Amperes.